UPS Runtime Calculator for Cameras, NVR, and PoE Switch

Add up the devices that must stay on during an outage, or type a total load. Then enter the UPS battery voltage, amp-hours, and number of batteries, or the battery energy in watt-hours.

1. Devices on the UPS

2. Your UPS

Total load–
Estimated runtime–
Load on your UPS–
Minimum UPS watts–
Minimum UPS VA–
Battery for your target–

The default devices are an example only. Replace them with the wattages on your own datasheets. Camera presets are the maximum power per PoE class at the switch port, so they give a worst case. The 80 percent efficiency is a planning assumption, not a manufacturer figure, and runtime is an upper estimate at high loads. Check the result against your UPS model’s runtime chart.

Camera Power by PoE Class

A PoE camera can draw up to 4.0 W on Class 1, 7.0 W on Class 2, 15.4 W on Class 3, and 30 W on Class 4 (PoE+), measured at the switch port. Eight Class 3 cameras can therefore add up to 123 W to your UPS load.

PoE classStandardMax power at switch port8 cameras16 cameras
Class 1802.3af4.0 W32 W64 W
Class 2802.3af7.0 W56 W112 W
Class 3802.3af15.4 W123 W246 W
Class 4802.3at (PoE+)30 W240 W480 W
Class 6802.3bt60 W480 W960 W
Class 8802.3bt90 W720 W1,440 W

Class limits from the Ethernet Alliance overview of IEEE 802.3bt. Most cameras draw less than their class maximum, so the camera’s own datasheet value gives a closer estimate.

How to Size a UPS for a Camera System

  1. List every device that must stay on. Cameras alone are not enough. The NVR records, the PoE switch powers the cameras, and the router sends alerts.
  2. Find real wattages. CyberPower suggests the user manual or safety label, or volts × amps when only current is listed. Schneider Electric notes that nameplate ratings are often higher than actual draw.
  3. Add 25 percent headroom. CyberPower recommends that the load not exceed 80 percent of the UPS capacity, so multiply the total by 1.25.
  4. Check both watts and VA. Divide the minimum watts by the UPS power factor to get the minimum VA, as in Eaton’s formula.
  5. Confirm runtime on the chart. Use the UPS maker’s runtime chart or selector tool for the final choice.

Formula vs. Manufacturer Runtime

The simple formula assumes a battery delivers the same energy at any load. It does not. CyberPower’s CP1500PFCLCD (1500 VA / 1000 W, two 12 V / 9 Ah batteries, 216 Wh) shows how far apart the two can be at high loads.

LoadFormula at 80% efficiencyCyberPower published runtime
Half load (500 W)20.7 min10 min
Full load (1000 W)10.4 min2.5 min

Formula values are calculated by SecurityTechLab from the published battery size. Typical camera systems load a UPS far below half, where the gap is smaller, but always check your model’s chart.

UPS Runtime Formulas

  • Total load (W) = cameras × watts per camera + NVR + PoE switch + other devices
  • Battery energy (Wh) = battery volts × amp-hours × number of batteries
  • Runtime (minutes) = battery Wh × efficiency ÷ load W × 60
  • Minimum UPS watts = total load × 1.25
  • Minimum UPS VA = minimum UPS watts ÷ power factor
  • Battery needed (Wh) = load W × target minutes ÷ 60 ÷ efficiency

Example: 8 Class 2 cameras at 7.0 W, a 25 W NVR, 10 W for the switch, and a 10 W router add up to 101 W. Two 12 V, 9 Ah batteries hold 216 Wh, so at 80 percent efficiency the formula gives about 103 minutes. The minimum UPS is about 127 W and 181 VA at a 0.7 power factor.

Limits of This Calculator

This is a planning estimate, not a guarantee. Battery age, temperature, and discharge rate change real runtime, and efficiency varies with load, as Schneider Electric explains. Infrared lights, heaters, and PTZ motors can raise camera draw at night or in cold weather. Use the result to shortlist UPS models, then confirm with the manufacturer’s runtime data.

Frequently Asked Questions

How long will a UPS run my security cameras and NVR?

Divide the battery energy the UPS can deliver by your total load. A UPS with two 12 V, 9 Ah batteries stores 216 Wh, so a 150 W camera system at 80 percent efficiency would run about 69 minutes by the formula. Check the result against the manufacturer’s runtime chart, because batteries deliver less energy at high loads.

What size UPS do I need for a security camera system?

Add up the watts of the cameras, NVR, PoE switch, and router, then multiply by 1.25 so the load stays under 80 percent of the UPS watt rating, as CyberPower recommends. Divide that by the UPS power factor to get the minimum VA. For a 150 W load and a 0.7 power factor, that is at least 188 W and 268 VA.

Should I count PoE camera watts and the PoE switch separately?

Yes. PoE cameras take their power through the switch, so the switch draws its own consumption plus the power it delivers to every camera. Count each camera once at its PoE class or datasheet wattage, then add the switch’s own consumption from its datasheet.

Why is the real runtime shorter than the formula?

Battery discharge is not linear. CyberPower lists 10 minutes at half load and 2.5 minutes at full load for its CP1500PFCLCD, which has 216 Wh of battery. At 500 W the simple formula at 80 percent efficiency gives about 21 minutes, so treat the formula as an upper estimate at high loads.

What is the difference between VA and watts on a UPS?

Watts are the real power your devices use, and VA is the apparent power the UPS must handle. The ratio is the power factor. Eaton gives the formula VA = watts ÷ power factor, and CyberPower’s CP1500PFCLCD is rated 1500 VA and 1000 W, a power factor of about 0.67.

Sources

All sources accessed November 2, 2026.

Plan the rest of your system

Check that your PoE switch can power every camera, then size the recorder’s storage. For the recorder itself, see what an NVR system is.

PoE Budget Calculator